Description
Thermon T-3 heat transfer compound is engineered to establish a highly efficient thermal bond between steam or electric heaters and process pipes or equipment. Its innovative formulation enhances heat transfer efficiency, offering a cost-effective alternative to traditional methods such as contoured clamp-on jackets. Remarkably, a single Thermonized steam tracer, combined with Thermon’s heat transfer compound, outperforms multiple bare tracers, providing equivalent performance while reducing costs.
T-3 is ideally suited for applications with maximum exposure temperatures of 371°C (700°F). To streamline installation and minimize waste, Thermon recommends utilizing their ChannelTrace™ system, featuring TFK channels. This system not only provides protection prior to thermal insulation installation but also eliminates the need for special curing procedures for the T-3 heat transfer compound.
With its exceptional heat transfer capabilities and compatibility with various heating systems, Thermon T-3 ensures efficient and reliable thermal performance in industrial applications. Whether used with steam or electric heaters, T-3 offers a cost-effective solution for enhancing heat transfer efficiency and optimizing thermal performance in diverse environments.
Container sizes | 3.79/18.93 liter |
---|---|
Maximum exposure temperature (ASTM C447) | 371°C (700°F) |
Minimum exposure temperature | -196°C (-320°F) |
Minimum installation temperature | 0°C (32°F) |
Heat transfer coefficient, Ut, tracer to pipe wall | 114-227 W/m2 . °C (20-40 Btu/hr . °F . ft2) |
Nominal electrical resistivity | 0.86 ohms-cm (0.34 ohms-inch) |
Shelf life (unopened) | 18 months |
Bond Strength (ASTM D1002) | > 1380 kPa (> 200 lbs/in2) |
Water Soluble Chlorides (ASTM C1218) | < 100 ppm |
Water-soluble | yes |
</p>
Reviews
There are no reviews yet.