Description
The RAYCHEM KTV self-regulating trace heating cable is engineered for process temperature maintenance of pipes and vessels that undergo steam cleaning, operating effectively up to 300°F/150°C. These cables are also ideal for freeze protection in systems with high heat losses, withstanding intermittent exposure to 482°F/250°C. Featuring a fluoropolymer outer jacket (-CT), these cables offer exceptional resistance against aggressive organics and corrosives.
Primarily designed for electrical heat tracing in process temperature maintenance applications up to 150°C, including those subject to steam cleaning, the KTV family of self-regulating, parallel circuit heating cables is versatile. They cater to frost protection in large pipes and applications necessitating high-temperature exposure capabilities. The KTV cables ensure reliable, long-lasting performance and compliance with hazardous area classifications.
- Simplified design for hazardous areas: unconditional T2C class, T3-T6 based on systems approach.
- Longer circuit lengths due to larger cross-section conductors.
- High power output for higher temperature applications.
- Swift installation: cut-to-length capability, flexibility, easy stripping, multiple overlaps allowed, meter markings, user-friendly connection kits.
- Safe and efficient operation: prevents overheating, maintains uniform pipe temperatures, incorporates energy-saving technology.
- Supply Voltage: 200 – 277 V
- Max. Continuous Exposure Temperature: 150 °C
- Max. Intermittent Exposure Temperature: 250 °C
- Max Cumulative Hours for Intermittent Exposure: 1000 h
- Min. Installation Temperature: -60 °C
- Area Classification: Non-Hazardous & Hazardous
- Outer Jacket Material: High Temperature Fluoropolymer